This table is designed
as a guide to the selection of combivent for the correct application.
Once the flue size has been calculated referring to the kilowatt rating
for that diameter, will indicate the suitable combivent size.
A square unit has more
free area available than a circular system, therefore, will be suitable for
higher appliance ratings than the equivalent circular units.
Square Units
|
Flue diameter |
125 |
150 |
175 |
200 |
250 |
310 |
350 |
400 |
450 |
500 |
550 |
600 |
650 |
700 |
750 |
| Combivent Size |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CV400 SQ |
70 |
60 |
|
|
|
|
|
|
|
|
|
|
|
|
|
| CV500 SQ |
180 |
170 |
160 |
150 |
110 |
|
|
|
|
|
|
|
|
|
|
| CV600 SQ |
|
|
300 |
290 |
255 |
220 |
175 |
|
|
|
|
|
|
|
|
| CV750 SQ |
|
|
|
|
500 |
465 |
420 |
365 |
310 |
240 |
|
|
|
|
|
| CV850 SQ |
|
|
|
|
|
680 |
635 |
560 |
460 |
455 |
385 |
|
|
|
|
| CV1000 SQ |
|
|
|
|
|
|
|
960 |
905 |
835 |
765 |
690 |
610 |
|
|
| CV1250 SQ |
|
|
|
|
|
|
|
|
|
1450 |
1375 |
1305 |
1220 |
1135 |
1040 |
|
The above are
Maximum Boiler KW ratings for Square Combivent terminals |
Circular and Mitred Units
|
Flue diameter |
125 |
150 |
175 |
200 |
250 |
310 |
350 |
400 |
450 |
500 |
550 |
600 |
650 |
700 |
750 |
| Combivent Size |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CV400 C/M |
35 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| CV500 C/M |
125 |
115 |
105 |
90 |
|
|
|
|
|
|
|
|
|
|
|
| CV600 C/M |
|
|
215 |
205 |
170 |
135 |
|
|
|
|
|
|
|
|
|
| CV750 C/M |
|
|
|
|
250 |
210 |
165 |
110 |
|
|
|
|
|
|
|
| CV850 C/M |
|
|
|
|
355 |
315 |
270 |
220 |
160 |
|
|
|
|
|
|
| CV1000 C/M |
|
|
|
|
|
480 |
435 |
385 |
320 |
252 |
185 |
|
|
|
|
| CV1250 C/M |
|
|
|
|
|
|
|
855 |
830 |
760 |
685 |
615 |
525 |
450 |
355 |
|
The above are
Maximum Boiler KW ratings for Circular and Mitred Combivent
terminals |
|